No success with StorEdge SE7K-RWS48BNN4 and SDM630MCT-RC + 3pcsESCT-RC100 #9
Comments
Did some more testing. No success but found something that seems a bit odd to me, but might have some explanation.
Log from @nmakel :
Looking at the bytes: Some of the data is diffrent due to some differences in settings. But why does the log from nmakel have 020300000031 in the beginning and after that almost matchning data? |
Great, thanks for trying this project out.
Shouldn't matter. I don't have CTs either, and everything works fine.
Looks good.
Those first few frame check errors might be due to an incomplete message still in the serial buffer. The last few lines look fine, though. The difference in logged requests might be due to me using the TCP version. The last few bytes are crc checks, and the first few bytes are RTU to TCP encapsulation. Still, you're running into similar issues as #8, so I'm wondering whether you can post the inverter firmware version you have. |
Hello! Thank you for the quick response. Too bad the thing i found wasn't an error. The "Not a valid unit id - 112, ignoring!!" errors I actually get constantly. It might have something to do with the fact that there seems to be something connected to the bus since there is a small pcb with a cable on it, in the RS485-1 port of the communication board of the inverter. Like a RS485 splitter. I was thinking it had something to do with the battery communication, even if the actual battery is connected to Canbus. Here are my versions: If it seems to be hard to find the issue for this problem we have, I might give it a try to find the modbus registers for the Inepro pro380 meter instead and try to fork your code to implement it's registers instead. |
I've managed to find a workaround to #8 by implemented a Janitza compatible metering proxy. With that I get actual powers reported, but the energy reporting is still off (whether I report all zero energy values or actuals). Pretty sure I'm using the right registers with the right values (any helpful ideas here might be helpful). I've had a version update since starting #8 and am now at version: |
Interesting. What model battery do you have connected?
Thanks. Just like @jonesPD you're on a newer firmware version than I am.
You can find the register map at the end of this document. It should be fairly simple to adapt the current script to the Inepro. Please share your results if you decide to try this! |
Please do! |
``> Interesting. What model battery do you have connected? It's actually a DIY battery but it's reporting data over canbus with same protocol as the LG Resu battery.
Ok!
Thank you. I actually already started and also found another document that better explained the settings registers better. I will report back with the results. So far no luck since it seems to get stuck at getting settings registers even here. Also a note.. I have actually confirmed that the battery has 112.
|
@jonesPD Thank you for the details. Is your Janitza implementation based on this code or a completely new project? So I have also been trying the Janizta now. With that setting, the inverter seems to start pulling data from the measurement registers right away, (19021 with a length of 24) but I still don't get it to work. I would be very happy if you could share your code and I can give that a go. You said you has issues with energy registers. One thing i noticed is that they should be stored in Wh in the Janizta but I get them in kWh from the SDM630. I'm not sure how yours are stored? Another thing that is on my mind is that the configuration in the setapp for me is missing the sunspec protocol in the menu for RS485-1. That might be a big deal? But I still can choose the other brands of meters like the PRO380 and Janitza. |
@djmoonshine: my code is attached, it is heavily based on this project, but not yet integrated so that you can for example select in the config file the type of meter you want to proxy. I've based it the register map in this PDF. The power readings seem to work fine, the energy reading is odd. I don't have a recent SetApp screenshot, and since the sun has almost set it is better to provide one tomorrow. In the solaredge app you can see a different chart that now shows not only the converted solar power, but also the consumed power, and self consumption in a single graph. As you can see in the screenshot though is that the energy totals are off (except for the system production), and that it doesn't show any exported energy. I haven't been able to fix this, and testing is also rather slow, because when the SE-server detects a major disruption in the data (e.g. when you change signs or start providing data), you have to wait until the next day for the graphs to come back). The code is needs some cleaning up, and integration with the original project. @djmoonshine : success in getting it to work! |
Thanks for posting your working example. I'll have a look at the differences and perhaps I can find the reason why the original isn't working on newer firmware versions. |
Could you also provide me with the configuration file you are using? |
@jonesPD Thank you so much for sharing your code. It actually kind of worked, but with some weird behavior in about the same way as your screenshot. The energy bugs the most. I actually found out that my exported energy likes to show the data for " Reactive power L2", but switches to the correct data to, so it can't be just something totally wrong with the registers in the code. Also as I have mentioned before. I get "meter communication error 3x6e" in the inverter. That error didn't just go away with this code, bacause that seems to be another issue. When I disable the battery communication the communication with the meter works fine, but with the battery activated i get those "Not a valid unit id - 112, ignoring!!" which i guess is normal, because it's the communication to the battery. But I also get a lot of "DEBUG: CRC invalid, discarding header!!" and almost no requests for data for the meter. So i assume the crc errors happens for the requests to the "meter". I have tried different configurations of termination resistors both at the inverter end with the dip switch both on and off (according to the manual it should be off) and also at the meter end (or actually in this case an USB adapter in a raspberry pi) but with no luck. So at the moment i cannot have the meter and battery running at the same time, and that is a big deal since a lot of the functionality i want with the battery, needs a import/export meter. Any suggestions? I have ordered a higher quality RS485 adapter to see if that is the issue. But it will not arrive until the end of the week. |
Just now I actually foud out an interesting thing. |
So if I put the export energy values in the L2 reactive power register, they show up as export energy in SetApp? Thanks for sharing I'll try that too
Have you tried connecting the meter and the battery to a separate RS485 port each? Are both set to the same baudrate (9600baud) and parity? |
I also get those every now and then and also have not been able to resolve them with updated pymodbus, cabling, terminator settings or another rs485 dongle. I actually had two dongles talking to one another, if I recall correctly without errors. |
@jonesPD, please also share your configuration file. @djmoonshine, while the battery modbus traffic might be reflected if you do not have proper termination resistors on the RS485 bus, there shouldn't be any timing or collission issues. The inverter is the only Modbus master on the bus, and the battery and meterproxy will only answer when spoken to. Could you share the make and model of your RS485 adapter? I agree with jonesPD that it may be better to move the meterproxy to the second RS485 input on your inverter. It would be helpful if you could also make a few screenshots of how the RS485-1, RS485-2 and subsequent meter is configured in SetApp. |
It should be part of the janitza.zip file in my earlier post. Otherwise it will take a few days before I have access to it. |
You're absolutely right. I must have missed it the first time around. |
@djmoonshine : Removing all other measured values from the return of the 'values' functions, I've now tried your suggestion to put the energy values in different registers and import/export energy meter values now show up in SetApp:
This seems very odd to me, all Janitza modbus register maps I've found on the web show these registers as respectively total real power, total apparent power and total reactive power (where total refers to their (vector) sum over 3 phases). I'll let it run like this for a few days to see the result in the monitoring app. Did you get any step further? |
Hi everyone. How did you resolve this problem finally? It looks like I've got similar problem. My meter (SDM630) is connected, SE shows status as OK but no valid serial or meter data is presented. |
I had wierd issues and since I use battery storage with my Solaredge inverter having a constant and reliable connection was very important i finally ended up buying a real Solaredge meter. Something like this:
|
Thank you for your response. It looks like SE is blocking something in new FW. |
Thanks for letting us know! I would be interested in hearing whether the timeout is the real culprit, and not just a problem with the registers that are being presented -- which is what the switch to the janitza mapping would suggest. It could of course be that SE applies more strict checks to verify the type of meter it is communicating with in newer firmware versions. Wouldn't be out of character. |
Would you mind sharing how you are reporting your battery data to SolarEdge? |
I'm setting up a new StorEdge inverter and already had a SDM630 so this code would fit perfect!
The setup might be a bit different since I don't have normal CT:s, but rogowski coils.
https://www.aliexpress.com/item/32994844856.html
Therefore i'm not 100% sure what CT value I should set and how it affects. Since the meter is reporting correct values I don't understand what exactly this setting does.
I have tried this config:
`
[server]
device = /dev/serial/by-id/usb-Silicon_Labs_CP2104_USB_to_UART_Bridge_Controller_0106F08D-if00-port0
meters = import_export
[import_export]
type=sdm630
device=/dev/serial/by-id/usb-Silicon_Labs_CP2104_USB_to_UART_Bridge_Controller_010D5A07-if00-port0
baud=9600
src_address=1
dst_address=2
refresh_rate = 5
ct_current = 5
`
Unfortunately I don't really manage to get it to work. My inverter says communication error 3x6e.
Getting data from the meter seems to work. But also getting some strange errors in the log.
The text was updated successfully, but these errors were encountered: