104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
atrium_with_fans.fds
Generated by PyroSim - Version 2015.3.0810
Oct 14, 2015 4:57:44 PM
&HEAD CHID='atrium_with_fans'/
&TIME T_END=500.0/
&DUMP RENDER_FILE='atrium_with_fans.ge1', COLUMN_DUMP_LIMIT=.TRUE.,
DT_RESTART=300.0/
&MESH ID='Mesh01-a', IJK=60,58,60, XB=0.0,30.0,-2.0,27.0,0.0,30.0/
&MESH ID='Mesh01-b', IJK=120,24,120, XB=0.0,30.0,27.0,33.0,0.0,30.0/
&MESH ID='Mesh01-c', IJK=60,58,60, XB=0.0,30.0,33.0,62.0,0.0,30.0/
&MESH ID='Mesh02', IJK=20,120,40, XB=10.0,20.0,0.0,60.0,30.0,50.0/
&REAC ID='PROPYLENE',
FYI='FM SNL FDS5 Validation',
FUEL='REAC_FUEL',
FORMULA='C3H6',
SOOT_YIELD=0.02/
&PROP ID='Cleary Ionization I1',
QUANTITY='CHAMBER OBSCURATION',
ALPHA_E=2.5,
BETA_E=-0.7,
ALPHA_C=0.8,
BETA_C=-0.9/
&DEVC ID='Smoke Detector', PROP_ID='Cleary Ionization I1', XYZ=25.0,10.0,5.5/
&DEVC ID='Smoke Detector01', PROP_ID='Cleary Ionization I1', XYZ=25.0,20.0,5.5/
&DEVC ID='Smoke Detector02', PROP_ID='Cleary Ionization I1', XYZ=25.0,30.0,5.5/
&DEVC ID='Smoke Detector03', PROP_ID='Cleary Ionization I1', XYZ=25.0,40.0,5.5/
&DEVC ID='Smoke Detector04', PROP_ID='Cleary Ionization I1', XYZ=25.0,50.0,5.5/
&CTRL ID='Fire Detector Control', FUNCTION_TYPE='ALL', LATCH=.TRUE.,
INPUT_ID='or'/
&CTRL ID='or', FUNCTION_TYPE='ANY', LATCH=.FALSE., INPUT_ID='Smoke
Detector','Smoke Detector01','Smoke Detector02','Smoke Detector03','Smoke
Detector04'/
&MATL ID='CONCRETE',
FYI='NBSIR 88-3752 - ATF NIST Multi-Floor Validation',
SPECIFIC_HEAT=1.04,
CONDUCTIVITY=1.8,
DENSITY=2280.0/
&SURF ID='Concrete',
RGB=146,202,166,
BACKING='VOID',
MATL_ID(1,1)='CONCRETE',
MATL_MASS_FRACTION(1,1)=1.0,
THICKNESS(1)=0.3/
&SURF ID='ADIABATIC',
COLOR='GRAY 80',
ADIABATIC=.TRUE./
&SURF ID='Burner',
COLOR='RED',
HRRPUA=555.6,
RAMP_Q='Burner_RAMP_Q'/
&RAMP ID='Burner_RAMP_Q', T=0.0, F=0.0/
&RAMP ID='Burner_RAMP_Q', T=1.0, F=1.0/
&RAMP ID='Burner_RAMP_Q', T=300.0, F=1.0/
&RAMP ID='Burner_RAMP_Q', T=301.0, F=0.0/
&RAMP ID='Burner_RAMP_Q', T=500.0, F=0.0/
&OBST XB=0.0,10.0,0.0,60.0,6.0,6.5, SURF_ID='INERT'/ Floor Plate
&OBST XB=0.0,10.0,0.0,60.0,12.0,12.5, SURF_ID='INERT'/ Floor Plate
&OBST XB=0.0,10.0,0.0,60.0,18.0,18.5, SURF_ID='INERT'/ Floor Plate
&OBST XB=0.0,10.0,0.0,60.0,24.0,24.5, SURF_ID='INERT'/ Floor Plate
&OBST XB=20.0,30.0,0.0,60.0,24.0,24.5, SURF_ID='INERT'/ Floor Plate
&OBST XB=20.0,30.0,0.0,60.0,18.0,18.5, SURF_ID='INERT'/ Floor Plate
&OBST XB=20.0,30.0,0.0,60.0,12.0,12.5, SURF_ID='INERT'/ Floor Plate
&OBST XB=20.0,30.0,0.0,60.0,6.0,6.5, SURF_ID='INERT'/ Floor Plate
&OBST XB=0.0,30.0,59.5,60.0,0.0,30.0, SURF_ID='Concrete'/ End Wall
&OBST XB=10.0,20.0,59.5,60.0,30.0,36.0, SURF_ID='Concrete'/ End Reservoir
&OBST XB=0.0,30.0,0.0,0.5,0.0,30.0, SURF_ID='Concrete'/ End Wall
&OBST XB=10.0,20.0,0.0,0.5,30.0,36.0, SURF_ID='Concrete'/ End Reservoir
&OBST XB=29.5,30.0,0.0,60.0,0.0,30.0, COLOR='INVISIBLE', SURF_ID='Concrete'/
Side Wall
&OBST XB=0.0,0.5,0.0,60.0,0.0,30.0, SURF_ID='Concrete'/ Side Wall
&OBST XB=20.0,30.0,0.0,60.0,29.5,30.0, SURF_ID='ADIABATIC'/ Roof
&OBST XB=0.0,10.0,0.0,60.0,29.5,30.0, SURF_ID='ADIABATIC'/ Roof
&OBST XB=10.0,10.5,0.0,60.0,29.5,36.0, SURF_ID='ADIABATIC'/ Reservoir 1
&OBST XB=19.5,20.0,0.0,60.0,29.5,36.0, COLOR='INVISIBLE', SURF_ID='ADIABATIC'/
Reservoir 2
&OBST XB=10.0,20.0,0.0,60.0,35.5,36.0, SURF_ID='ADIABATIC'/ Reservoir 3
&OBST XB=20.0,23.0,28.5,31.5,0.0,0.5, SURF_IDS='Burner','INERT','INERT'/ Burner
&HOLE XB=12.5,17.5,59.0,60.5,-0.1,5.0/ End Door
&HOLE XB=12.5,17.5,-0.5,1.0,-0.1,5.0/ End Door
&VENT SURF_ID='OPEN', XB=30.0,30.0,60.0,62.0,0.0,30.0, COLOR='INVISIBLE'/ Mesh
Vent: Mesh01-c [XMAX]
&VENT SURF_ID='OPEN', XB=0.0,0.0,60.0,62.0,0.0,30.0, COLOR='INVISIBLE'/ Mesh
Vent: Mesh01-c [XMIN]
&VENT SURF_ID='OPEN', XB=0.0,30.0,62.0,62.0,0.0,30.0, COLOR='INVISIBLE'/ Mesh
Vent: Mesh01-c [YMAX]
&VENT SURF_ID='OPEN', XB=0.0,30.0,60.0,62.0,30.0,30.0, COLOR='INVISIBLE'/ Mesh
Vent: Mesh01-c [ZMAX]
&VENT SURF_ID='OPEN', XB=20.0,20.0,0.0,60.0,36.0,50.0, COLOR='INVISIBLE'/ Mesh
Vent: Mesh02 [XMAX]
&VENT SURF_ID='OPEN', XB=10.0,10.0,0.0,60.0,36.0,50.0, COLOR='INVISIBLE'/ Mesh
Vent: Mesh02 [XMIN]
&VENT SURF_ID='OPEN', XB=10.0,20.0,60.0,60.0,36.0,50.0, COLOR='INVISIBLE'/ Mesh
Vent: Mesh02 [YMAX]
&VENT SURF_ID='OPEN', XB=10.0,20.0,0.0,0.0,36.0,50.0, COLOR='INVISIBLE'/ Mesh
Vent: Mesh02 [YMIN]
&VENT SURF_ID='OPEN', XB=10.0,20.0,0.0,60.0,50.0,50.0, COLOR='INVISIBLE'/ Mesh
Vent: Mesh02 [ZMAX]
&VENT SURF_ID='OPEN', XB=30.0,30.0,-2.0,0.0,0.0,30.0, COLOR='INVISIBLE'/ Mesh
Vent: Mesh01-a [XMAX]
&VENT SURF_ID='OPEN', XB=0.0,0.0,-2.0,0.0,0.0,30.0, COLOR='INVISIBLE'/ Mesh
Vent: Mesh01-a [XMIN]
&VENT SURF_ID='OPEN', XB=0.0,30.0,-2.0,-2.0,0.0,30.0, COLOR='INVISIBLE'/ Mesh
Vent: Mesh01-a [YMIN]
&VENT SURF_ID='OPEN', XB=0.0,30.0,-2.0,0.0,30.0,30.0, COLOR='INVISIBLE'/ Mesh
Vent: Mesh01-a [ZMAX]
&VENT SURF_ID='Concrete', XB=0.0,30.0,-2.0,62.0,0.0,0.0/ Floor
&VENT ID='Extraction Bottom', SURF_ID='HVAC', XB=12.0,14.0,5.0,7.0,35.49,35.49/
&VENT ID='Extraction Top', SURF_ID='HVAC', XB=12.0,14.0,5.0,7.0,36.01,36.01/
&VENT ID='Extraction Bottom01', SURF_ID='HVAC',
XB=12.0,14.0,20.0,22.0,35.49,35.49/
&VENT ID='Extraction Top01', SURF_ID='HVAC',
XB=12.0,14.0,20.0,22.0,36.01,36.01/
&VENT ID='Extraction Bottom02', SURF_ID='HVAC',
XB=12.0,14.0,35.0,37.0,35.49,35.49/
&VENT ID='Extraction Top02', SURF_ID='HVAC',
XB=12.0,14.0,35.0,37.0,36.01,36.01/
&VENT ID='Extraction Bottom03', SURF_ID='HVAC',
XB=12.0,14.0,50.0,52.0,35.49,35.49/
&VENT ID='Extraction Top03', SURF_ID='HVAC',
XB=12.0,14.0,50.0,52.0,36.01,36.01/
&VENT ID='Extraction Bottom04', SURF_ID='HVAC',
XB=16.0,18.0,5.0,7.0,35.49,35.49/
&VENT ID='Extraction Top04', SURF_ID='HVAC', XB=16.0,18.0,5.0,7.0,36.01,36.01/
&VENT ID='Extraction Bottom05', SURF_ID='HVAC',
XB=16.0,18.0,20.0,22.0,35.49,35.49/
&VENT ID='Extraction Top05', SURF_ID='HVAC',
XB=16.0,18.0,20.0,22.0,36.01,36.01/
&VENT ID='Extraction Bottom06', SURF_ID='HVAC',
XB=16.0,18.0,35.0,37.0,35.49,35.49/
&VENT ID='Extraction Top06', SURF_ID='HVAC',
XB=16.0,18.0,35.0,37.0,36.01,36.01/
&VENT ID='Extraction Bottom07', SURF_ID='HVAC',
XB=16.0,18.0,50.0,52.0,35.49,35.49/
&VENT ID='Extraction Top07', SURF_ID='HVAC',
XB=16.0,18.0,50.0,52.0,36.01,36.01/
&HVAC ID='Middle', TYPE_ID='NODE', DUCT_ID='Damper Duct','Fan Duct',
XYZ=13.0,6.0,35.75/
&HVAC ID='Extraction Bottom', TYPE_ID='NODE', DUCT_ID='Damper Duct',
VENT_ID='Extraction Bottom'/
&HVAC ID='Extraction Top', TYPE_ID='NODE', DUCT_ID='Fan Duct',
VENT_ID='Extraction Top'/
&HVAC ID='Damper Duct', TYPE_ID='DUCT', AREA=4.0, PERIMETER=8.0, DAMPER=.TRUE.,
NODE_ID='Extraction Bottom','Middle', ROUGHNESS=0.001, LENGTH=0.26,
CTRL_ID='Fire Detector Control'/
&HVAC ID='Fan Duct', TYPE_ID='DUCT', AREA=4.0, PERIMETER=8.0, FAN_ID='Smoke
Fan', NODE_ID='Middle','Extraction Top', ROUGHNESS=0.001, LENGTH=0.26/
&HVAC ID='Middle01', TYPE_ID='NODE', DUCT_ID='Damper Duct01','Fan Duct01',
XYZ=13.0,21.0,35.75/
&HVAC ID='Extraction Bottom01', TYPE_ID='NODE', DUCT_ID='Damper Duct01',
VENT_ID='Extraction Bottom01'/
&HVAC ID='Extraction Top01', TYPE_ID='NODE', DUCT_ID='Fan Duct01',
VENT_ID='Extraction Top01'/
&HVAC ID='Damper Duct01', TYPE_ID='DUCT', AREA=4.0, PERIMETER=8.0,
DAMPER=.TRUE., NODE_ID='Extraction Bottom01','Middle01', ROUGHNESS=0.001,
LENGTH=0.26, CTRL_ID='Fire Detector Control'/
&HVAC ID='Fan Duct01', TYPE_ID='DUCT', AREA=4.0, PERIMETER=8.0, FAN_ID='Smoke
Fan', NODE_ID='Middle01','Extraction Top01', ROUGHNESS=0.001, LENGTH=0.26/
&HVAC ID='Middle02', TYPE_ID='NODE', DUCT_ID='Damper Duct02','Fan Duct02',
XYZ=13.0,36.0,35.75/
&HVAC ID='Extraction Bottom02', TYPE_ID='NODE', DUCT_ID='Damper Duct02',
VENT_ID='Extraction Bottom02'/
&HVAC ID='Extraction Top02', TYPE_ID='NODE', DUCT_ID='Fan Duct02',
VENT_ID='Extraction Top02'/
&HVAC ID='Damper Duct02', TYPE_ID='DUCT', AREA=4.0, PERIMETER=8.0,
DAMPER=.TRUE., NODE_ID='Extraction Bottom02','Middle02', ROUGHNESS=0.001,
LENGTH=0.26, CTRL_ID='Fire Detector Control'/
&HVAC ID='Fan Duct02', TYPE_ID='DUCT', AREA=4.0, PERIMETER=8.0, FAN_ID='Smoke
Fan', NODE_ID='Middle02','Extraction Top02', ROUGHNESS=0.001, LENGTH=0.26/
&HVAC ID='Middle03', TYPE_ID='NODE', DUCT_ID='Damper Duct03','Fan Duct03',
XYZ=13.0,51.0,35.75/
&HVAC ID='Extraction Bottom03', TYPE_ID='NODE', DUCT_ID='Damper Duct03',
VENT_ID='Extraction Bottom03'/
&HVAC ID='Extraction Top03', TYPE_ID='NODE', DUCT_ID='Fan Duct03',
VENT_ID='Extraction Top03'/
&HVAC ID='Damper Duct03', TYPE_ID='DUCT', AREA=4.0, PERIMETER=8.0,
DAMPER=.TRUE., NODE_ID='Extraction Bottom03','Middle03', ROUGHNESS=0.001,
LENGTH=0.26, CTRL_ID='Fire Detector Control'/
&HVAC ID='Fan Duct03', TYPE_ID='DUCT', AREA=4.0, PERIMETER=8.0, FAN_ID='Smoke
Fan', NODE_ID='Middle03','Extraction Top03', ROUGHNESS=0.001, LENGTH=0.26/
&HVAC ID='Middle04', TYPE_ID='NODE', DUCT_ID='Damper Duct04','Fan Duct04',
XYZ=17.0,6.0,35.75/
&HVAC ID='Extraction Bottom04', TYPE_ID='NODE', DUCT_ID='Damper Duct04',
VENT_ID='Extraction Bottom04'/
&HVAC ID='Extraction Top04', TYPE_ID='NODE', DUCT_ID='Fan Duct04',
VENT_ID='Extraction Top04'/
&HVAC ID='Damper Duct04', TYPE_ID='DUCT', AREA=4.0, PERIMETER=8.0,
DAMPER=.TRUE., NODE_ID='Extraction Bottom04','Middle04', ROUGHNESS=0.001,
LENGTH=0.26, CTRL_ID='Fire Detector Control'/
&HVAC ID='Fan Duct04', TYPE_ID='DUCT', AREA=4.0, PERIMETER=8.0, FAN_ID='Smoke
Fan', NODE_ID='Middle04','Extraction Top04', ROUGHNESS=0.001, LENGTH=0.26/
&HVAC ID='Middle05', TYPE_ID='NODE', DUCT_ID='Damper Duct05','Fan Duct05',
XYZ=17.0,21.0,35.75/
&HVAC ID='Extraction Bottom05', TYPE_ID='NODE', DUCT_ID='Damper Duct05',
VENT_ID='Extraction Bottom05'/
&HVAC ID='Extraction Top05', TYPE_ID='NODE', DUCT_ID='Fan Duct05',
VENT_ID='Extraction Top05'/
&HVAC ID='Damper Duct05', TYPE_ID='DUCT', AREA=4.0, PERIMETER=8.0,
DAMPER=.TRUE., NODE_ID='Extraction Bottom05','Middle05', ROUGHNESS=0.001,
LENGTH=0.26, CTRL_ID='Fire Detector Control'/
&HVAC ID='Fan Duct05', TYPE_ID='DUCT', AREA=4.0, PERIMETER=8.0, FAN_ID='Smoke
Fan', NODE_ID='Middle05','Extraction Top05', ROUGHNESS=0.001, LENGTH=0.26/
&HVAC ID='Middle06', TYPE_ID='NODE', DUCT_ID='Damper Duct06','Fan Duct06',
XYZ=17.0,36.0,35.75/
&HVAC ID='Extraction Bottom06', TYPE_ID='NODE', DUCT_ID='Damper Duct06',
VENT_ID='Extraction Bottom06'/
&HVAC ID='Extraction Top06', TYPE_ID='NODE', DUCT_ID='Fan Duct06',
VENT_ID='Extraction Top06'/
&HVAC ID='Damper Duct06', TYPE_ID='DUCT', AREA=4.0, PERIMETER=8.0,
DAMPER=.TRUE., NODE_ID='Extraction Bottom06','Middle06', ROUGHNESS=0.001,
LENGTH=0.26, CTRL_ID='Fire Detector Control'/
&HVAC ID='Fan Duct06', TYPE_ID='DUCT', AREA=4.0, PERIMETER=8.0, FAN_ID='Smoke
Fan', NODE_ID='Middle06','Extraction Top06', ROUGHNESS=0.001, LENGTH=0.26/
&HVAC ID='Middle07', TYPE_ID='NODE', DUCT_ID='Damper Duct07','Fan Duct07',
XYZ=17.0,51.0,35.75/
&HVAC ID='Extraction Bottom07', TYPE_ID='NODE', DUCT_ID='Damper Duct07',
VENT_ID='Extraction Bottom07'/
&HVAC ID='Extraction Top07', TYPE_ID='NODE', DUCT_ID='Fan Duct07',
VENT_ID='Extraction Top07'/
&HVAC ID='Damper Duct07', TYPE_ID='DUCT', AREA=4.0, PERIMETER=8.0,
DAMPER=.TRUE., NODE_ID='Extraction Bottom07','Middle07', ROUGHNESS=0.001,
LENGTH=0.26, CTRL_ID='Fire Detector Control'/
&HVAC ID='Fan Duct07', TYPE_ID='DUCT', AREA=4.0, PERIMETER=8.0, FAN_ID='Smoke
Fan', NODE_ID='Middle07','Extraction Top07', ROUGHNESS=0.001, LENGTH=0.26/
&HVAC ID='Smoke Fan', TYPE_ID='FAN', MAX_FLOW=16.0, MAX_PRESSURE=1.0E4/
&SLCF QUANTITY='VELOCITY', VECTOR=.TRUE., PBX=15.0/
&SLCF QUANTITY='TEMPERATURE', PBX=15.0/
&SLCF QUANTITY='VISIBILITY', PBX=15.0/
&SLCF QUANTITY='VELOCITY', VECTOR=.TRUE., PBY=30.0/
&SLCF QUANTITY='TEMPERATURE', PBY=30.0/
&SLCF QUANTITY='VISIBILITY', PBY=30.0/
&TAIL /